Mecer Galleon II 3-phase 10Kva 10Kw Online Tower UPS ME-10K-GA33
Features
- True double-conversion
- DSP technology guarantees high performance
- Output power factor 1
- Active power factor correction in all phases
- 50Hz/60Hz frequency converter mode
- ECO mode operation for energy saving (ECO)
- Emergency power off function (EPO)
- Generator compatible
- SNMP+USB+RS-232 multiple communications
- 3-stage extendable charging design for optimized battery performance
- Adjustable battery numbers for long-run model
- Maintenance bypass available
- Parallel operation with commom battery
- Power walk-in function
- *Optional parallel operation
- *Optional isolation transformer offers full isolation and complete common mode noise rejection
Technical Specification
Product: Mecer Galleon II 3-phase UPS
Phase: 3-phase in/3-phase out
Capacity: 10KVA/10KW
Parallel Capability: Up to 4 units
INPUT
-
Nominal Voltage: 3X400Vac(3Ph+N)/230Vac(1Ph=N)
-
Voltage Range: 110-300 VAC @ 50% loadï¼›176-276 VAC @ 100% load
-
Frequency Range: 46-54Hz or 56-64Hz
-
Power Factor: 0.99 @ 100% load
-
Harmonic Distortion (THDi): < 4% at full linear load
OUTPUT
- Output Voltage: 3 x380/400/415 VAC (3Ph+N) or 208/220/230/240 VAC (1Ph+N)
- AC Voltage Regulation (Batt. Mode): ± 1%
- Frequency Range (Synchronized Range): 46-54Hz or 56-64Hz
- Frequency Range (Batt. Mode): 50/60 Hz ± 1% or 60Hz ± 0.1 Hz
- Current Crest Ratio: 3:1 (max.)
- Harmonic Distortion (THDv): 2% THD (Linear Load) , 5% THD (Non-linear Load)
Transfer Time
-
AC mode to Battery mode: Zero
-
Inverter to Bypass: Zero
Waveform (Batt. Mode): Pure Sine Wave
Overload Capability
-
AC mode: 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately
-
Battery Mode: 100-110% for 60 min, 110-125% for 10 min, 125%~150% for 1 min; >150% immediately
BYPASS
- Nominal Voltage: 3 x 380/400/415 VAC (3Ph+N)
- Voltage Range: -30% to +20% (Adjustable)
- Frequency Range (Synchronized Range): 46-54Hz or 56-64Hz
- Overload Capability: > 130% 1 minute (default)Continously working until breaker protection (optional)
BATTERY
- Battery Type: 12V/9Ah
- Numbers: (10+10)pcs
- Typical Recharge Time: 4 hours recover to 90% capacity
- Charging Current (max.): 2A (Adjustable)
- Charging Voltage: +/-13.65V*N (N=10)
INDICATORS
LCD Panel: UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
MANAGEMENT
- Smart RS-232/USB: Supports Windows® Family, Linux and MAC
- Optional SNMP: Power management from SNMP manager and web browser
Dimension, D X W X H (mm): 630 x 250 x 826
Weight: 103 kg
*When output voltage is set as 3 x 360VAC, the output power of the unit will be de-rated to 90%.
**If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.